Brauntacho Vietnam, Protection systems, Single Channel for 1oo1, 1oo2 and 2oo2 solutions, Triple Channel (TMR) for 2oo3 solutions, OEM specific Protection Systems, Brauntacho Việt Nam
E16 System product matrix (overview), Standard solutions in 2oo3 architecture
| Model | SIL3 | SIL2 | PFD Value | Test Interface | Test Generator | Automatic Test of 2oo3 Solenoid by E16 | PROFIBUS Interface |
| E16x342 | ● | 7,71 · 10-5 | ● | 1 | |||
| E16x352 | ● | 7,71 · 10-5 | ● | 2 | |||
| E16x346 | ● | 8,41 · 10-6 | ● | ● | 1 | ||
| E16x356 | ● | 8,41 · 10-6 | ● | ● | 2 | ||
| E16x442 | ● | 1,81 · 10-4 | ● | 1 | |||
| E16x452 | ● | 1,81 · 10-4 | ● | 2 | |||
| E16x446 | ● | 2,51 · 10-5 | ● | ● | 1 | ||
| E16x456 | ● | 2,51 · 10-5 | ● | ● | 2 |
Protection Systems for highest safety requirements up to SIL 3
E16x342
Monitoring and Protection System E16x342 for highest safety requirements up to SIL3
- TMR (triple-modular-redundant) system with sensor monitoring and self-test
- Highest safety levels with maximum availability by globally unique and true 2oo3 architecture for each trip criterion within each of the three Monitors
- Maintenance-free during lifetime due to integrated automatic proof tests
- External test of a 2oo3 solenoid valve block possible via the control system
- Minimal Total Cost of Ownership
- Requires less than 8% of the permissible PFD value for a SIL3 Safety Loop
- Replacement of all active components during operation (Hot Swap)
- TÜV certified for SIL3 / IEC 61508:2010
- TÜV certified for PL e; Cat. 3 / DIN EN ISO 13849-1:2008
- TÜV certified for SILCL3 / IEC 62061:2005
- API670 and API612 compliant
- 1 PROFIBUS Interface
E16x352
Monitoring and Protection System E16x352 for highest safety requirements up to SIL3
- TMR (triple-modular-redundant) system with sensor monitoring and self-test
- Highest safety levels with maximum availability by globally unique and true 2oo3 architecture for each trip criterion within each of the three Monitors
- Maintenance-free during lifetime due to integrated automatic proof tests
- External test of a 2oo3 solenoid valve block possible via the control system
- Minimal Total Cost of Ownership
- Requires less than 8% of the permissible PFD value for a SIL3 Safety Loop
- Replacement of all active components during operation (Hot Swap)
- TÜV certified for SIL3 / IEC 61508:2010
- TÜV certified for PL e; Cat. 3 / DIN EN ISO 13849-1:2008
- TÜV certified for SILCL3 / IEC 62061:2005
- API670 and API612 compliant
- 2 PROFIBUS Interfaces
E16x346
Monitoring and Protection System E16x346 for highest safety requirements up to SIL3
- TMR (triple-modular-redundant) system with sensor monitoring and self-test
- Highest safety levels with maximum availability by globally unique and true 2oo3 architecture for each trip criterion within each of the three Monitors
- Maintenance-free during lifetime due to integrated automatic proof tests
- Automated tests of a 2oo3 solenoid valve block with permanent monitoring of the feedback via the test generator
- Minimal Total Cost of Ownership
- Requires less than 1% of the permissible PFD value for a SIL3 Safety Loop
- Enhanced safety values due to an integrated test generator
- Replacement of all active components during operation (Hot Swap)
- TÜV certified for SIL3 / IEC 61508:2010
- TÜV certified for PL e; Cat. 3 / DIN EN ISO 13849-1:2008
- TÜV certified for SILCL3 / IEC 62061:2005
- API670 and API612 compliant
- 1 PROFIBUS Interface
E16x356
Monitoring and Protection System E16x356 for highest safety requirements up to SIL3
- TMR (triple-modular-redundant) system with sensor monitoring and self-test
- Highest safety levels with maximum availability by globally unique and true 2oo3 architecture for each trip criterion within each of the three Monitors
- Maintenance-free during lifetime due to integrated automatic proof tests
- Automated tests of a 2oo3 solenoid valve block with permanent monitoring of the feedback via the test generator
- Minimal Total Cost of Ownership
- Requires less than 1% of the permissible PFD value for a SIL3 Safety Loop
- Enhanced safety values due to an integrated test generator
- Replacement of all active components during operation (Hot Swap)
- TÜV certified for SIL3 / IEC 61508:2010
- TÜV certified for PL e; Cat. 3 / DIN EN ISO 13849-1:2008
- TÜV certified for SILCL3 / IEC 62061:2005
- API670 and API612 compliant
- 2 PROFIBUS Interfaces
E16x442
Monitoring and Protection System E16x442 for increased safety requirements up to SIL2
- TMR (triple-modular-redundant) system with sensor monitoring and self-test
- Highest safety levels with maximum availability by globally unique and true 2oo3 architecture for each trip criterion within each of the three Monitors
- Maintenance-free during lifetime due to integrated automatic proof tests
- External test of a 2oo3 solenoid valve block possible via the control system
- Minimal Total Cost of Ownership
- Requires less than 8% of the permissible PFD value for a SIL2 Safety Loop
- Replacement of all active components during operation (Hot Swap)
- SIL2 / IEC 61508:2010 compliant
- API670 and API612 compliant
- 1 PROFIBUS Interface
E16x452
Monitoring and Protection System E16x452 for increased safety requirements up to SIL2
- TMR (triple-modular-redundant) system with sensor monitoring and self-test
- Highest safety levels with maximum availability by globally unique and true 2oo3 architecture for each trip criterion within each of the three Monitors
- Maintenance-free during lifetime due to integrated automatic proof tests
- External test of a 2oo3 solenoid valve block possible via the control system
- Minimal Total Cost of Ownership
- Requires less than 8% of the permissible PFD value for a SIL2 Safety Loop
- Replacement of all active components during operation (Hot Swap)
- SIL2 / IEC 61508:2010 compliant
- API670 and API612 compliant
- 2 PROFIBUS Interfaces
E16x446
Monitoring and Protection System E16x446 for increased safety requirements up to SIL2
- TMR (triple-modular-redundant) system with sensor monitoring and self-test
- Highest safety levels with maximum availability by globally unique and true 2oo3 architecture for each trip criterion within each of the three Monitors
- Maintenance-free during lifetime due to integrated automatic proof tests
- Automated tests of a 2oo3 solenoid valve block with permanent monitoring of the feedback via the test generator
- Minimal Total Cost of Ownership
- Requires less than 1% of the permissible PFD value for a SIL2 Safety Loop
- Enhanced safety values due to an integrated test generator
- Replacement of all active components during operation (Hot Swap)
- SIL2 / IEC 61508:2010 compliant
- API670 and API612 compliant
- 1 PROFIBUS Interface
E16x456
Monitoring and Protection System E16x456 for increased safety requirements up to SIL2
- TMR (triple-modular-redundant) system with sensor monitoring and self-test
- Highest safety levels with maximum availability by globally unique and true 2oo3 architecture for each trip criterion within each of the three Monitors
- Maintenance-free during lifetime due to integrated automatic proof tests
- Automated tests of a 2oo3 solenoid valve block with permanent monitoring of the feedback via the test generator
- Minimal Total Cost of Ownership
- Requires less than 1% of the permissible PFD value for a SIL2 Safety Loop
- Enhanced safety values due to an integrated test generator
- Replacement of all active components during operation (Hot Swap)
- SIL2 / IEC 61508:2010 compliant
- API670 and API612 compliant
- 2 PROFIBUS Interfaces